Connection & Settings#

Achtung

Es ist wichtig, die DIP-Schalterstellung auf DCF zu konfigurieren.

Connect the DCF receiver (AD 650) to the clock terminal board placed on the anchoring plate (LINE IN terminal) using an unshielded two-wire cable with double insulation (a 10 m cable is included in the delivery). The maximum length of the cable depends on its cross-section (at least 0.25 mm²) and can be up to 200 m. We recommend using shielded cable only in critical conditions.

The functionality of the receiver is independent of the connection polarity. Cut the cable to the required length.

With good reception, the LED on the receiver flashes once per second with a skip of 1 pulse at the 59th second.

Standard-Anschluss#

Drahtfarbe

Anschluss

Weiß

LINES +

Braun

LINES −

../../../_images/dcf.svg ../../../_images/dcf-dark.svg

ECO-DC Anschluss#

Achtung

Connect one pin (LINES+ or LINES-) to the PE conductor.

Drahtfarbe

Anschluss

Weiß

LINES IN +

Braun

LINES IN −

Yellow / Green (PE conductor)

Either LINES IN + or LINES IN −

../../../_images/dcf-eco-dc.svg ../../../_images/dcf-eco-dc-dark.svg

Einstellungen der Digitaluhr#

  1. Enter the digital clock menu, navigate to the SYNC submenu and proceed to enter.

  2. Navigate to item o1 and set it to value A (autodetection).

  3. Navigate then to item o2 and set it to value A (autodetection).

  4. Return to digital clock menu, navigate to the dISP submenu and proceed to enter.

  5. Navigate to item d2 and set it to value A (automatically set timezone).