Connection & Settings#
Attention
Il est important de configurer la position du commutateur DIP sur DCF.
Connect the DCF receiver (AD 650) to the clock terminal board placed on the anchoring plate (LINE IN terminal) using an unshielded two-wire cable with double insulation (a 10 m cable is included in the delivery). The maximum length of the cable depends on its cross-section (at least 0.25 mm²) and can be up to 200 m. We recommend using shielded cable only in critical conditions.
The functionality of the receiver is independent of the connection polarity. Cut the cable to the required length.
With good reception, the LED on the receiver flashes once per second with a skip of 1 pulse at the 59th second.
Raccordement standard#
Couleur du fil |
Connecteur |
---|---|
Blanc |
LINES + |
Marron |
LINES − |
Connexion ECO-DC#
Attention
Connect one pin (LINES+ or LINES-) to the PE conductor.
Couleur du fil |
Connecteur |
---|---|
Blanc |
LINES IN + |
Marron |
LINES IN − |
Yellow / Green (PE conductor) |
Either LINES IN + or LINES IN − |
Réglages de l’horloge numérique#
Enter the digital clock menu, navigate to the
SYNC
submenu and proceed to enter.Navigate to item
o1
and set it to valueA
(autodetection).Navigate then to item
o2
and set it to valueA
(autodetection).Return to digital clock menu, navigate to the
dISP
submenu and proceed to enter.Navigate to item
d2
and set it to valueA
(automatically set timezone).