Current Limits#

Setting of current limits for outputs.

In Service menu press the > button to select Current limits and proceed to enter its setting by pressing v button.

The display shows following:

L1:  150  DC: 50
Accu: 50 A: 0.1W

L1:  150:

Current limit for slave line (current, which is reached, master clock reports overload state)

DC: 50:

Current limit for 24 V output

Accu: 50:

Current limit for Accu (14 V) output

A: 0.1W:

Available power in Watts, which can be distributed into ouputs (cannot be set)

The current limits are in mA.

Summary available power (A:) is calculated by formula:

P[W] = 8.3 – Accu[A] × 14 + (Line[A] + DC[A]) × 25

Button function

v:

Enter item setting

x:

Return to Service menu

Button function in ‘item edit’ mode

< >:

Move between items

+ -:

Switch flasing item (holding down the button will cycle through the options)

v:

Save edited values and return to page view

x:

Exit without save and return to page view

After setting desired current limits, press the v button to confirm your choice. The display shows Saved and returns to page view.

Default Values#

Slave line:

L1: 150 [mA]

Output 24V:

DC: 70 [mA]

Output 14V:

Accu: 200 [mA]

Limits for Outputs#

Slave line:

L1: 150 [mA]

Output 24V:

DC: 200 [mA]

Output 14V:

Accu: 200 [mA]